CommunicationsAdapterRegisterMapping
20
18
3.1 I/OwordsandIDcode
AftertheI/Omoduleispowered-up,theidentificationcode(IDcode)ofthe
modulebaseisautomaticallyreadbythecommunicationadapter.TheID-code
providestheInterbusmasterwiththetypeofdata(inputoroutput)andthenumber
ofwordsinthemessageforeachmodule.AftertheI/Omodulesidentification
codesarereceived,theInterbusmasterwillautomaticallybegintheexecutionof
I/Odatacommunicationinrealtime.
ThelengthisineachcaseexpressedinI-orO-words,withthehighernumber
beingthedecisivefactor.Thenumberofwordsitcancontainis:1to10,12,14,
16,24or32words.
Example
TheIDcode forthe170ADM35010is0103hex.
H 01=Length statement, indicating thatthemodule needs oneword(I
orOword) fordatatransfer
H 03=Module Type,indicates thatthismodule hasinputs andoutputs
Table 3 I/OBaseWordNumber andIDCode(analog I/Obases)
Description
Function IWords OWords IDCode
170AAI14000 16inputchannels 16 4 1033hex
1651dec
170AAI52040 4inputchannels,RTD,Therm. 4 4 0433hex
0451dec
170AAO12000 4outputchannels,0...20mA 5 0531hex
0549dec
170AAO92100 4outputchannels,4...20mA 5 0531hex
0549dec
170AMM09000 4inputs,2outputs(discrete)
4input&2outputchannels(ana-
log)
1
4
1
4
0533hex
0551dec
Example