Interbus with TSX Momentum
20
8
reported to the master. This condition is visually signalled through the status LEDs
(WG, WR), also refer to to the LED status displays table (page 22).
Any I/O error reported by an I/O base is sent as a module error to the bus master
through the Interbus.
1.2.5
Light Level Test Function
The Test pushbutton can verify optical transmission quality without the need for
an additional measuring instrument. With the Interbus properly installed, a press of
the pushbutton starts testing. This causes the incoming light level to be
registered and qualitatively evaluated. If neither the WR nor the WG status LED
lights when the pushbutton is pressed, then the incoming light level is at least
22 dBm.
Possible causes if either the WR or WG status LED should light when the
pushbutton is pressed:
H The transmission path is too long > select another type of medium/adapter,
or make use of a repeater
H The bending radius is too small > choose a larger radius
H Bad connector quality, dirty lens (needs cleaning), or fiber end scratched
(polish)
H Broken fiber