Communications Adapter Register Mapping
17
Width: 178 mm
Height: 216 mm
20
2.2.2 Addressing for Analog I/O Bases
I/O data sent to and from the bus master is mapped to the terminals of analog I/O
bases in the following manner:
H Each analog value is mapped to a single word.
H The higher value word (MSW) is the first to be sent or received.
H Those words sent to the I/O base (output words) from the communications
adapter represent the output values and parameters.
H Words sent to the communications adapter (input words) from the I/O base
represent input values and statuses.
An example of register mapping for an analog I/O base is shown:
Register mapping for the 170 AAI 140 00 (16 input channels)
170 AAI 140 00 input data
MSW = word 16
Word 15
Word 5
Channel 16 value
Channel 15 value
Channel 5 value
Word 4
Word 3
Word 2
LSW = word 1
Channel 4 value
Channel 3 value
Channel 2 value
Channel 1 value
170 AAI 140 00 output data
MSW = word 16
Word 15
Word 5
No value
No value
No value
Word 4
Word 3
Word 2
LSW = word 1
Channel 5 ... 8 parameters
Channel 1 ... 4 parameters
Channel 13 ... 16 parameters
Channel 9 ... 12 parameters
to to
Additional Documentation: Further information can be found in the 870 USE
002 00 User Manual.