Intelligent/Special Purpose
35013379 02 October 2007 349
If configured for two 32 bit Counters - NO Output Assert, the following figures, which
show the 4X through 4X+4 counters, with low and high word, are displayed.
Note: Zero set into any 4X register pair for 32 bit values or any 4X register means
no change.
16151413121110987654321
4X
1 = Enable Counter 1
1 = Disable Counter 1
1 = Preset Counter 2
1 = Enable Counter 2
1 = Disable Counter 2
Load Values Command
Bit
1 = Preset Counter 1
Maximum Count for Counter 1 (max = 7FFFFFFF hex)
16151413121110987654321
4X+1 (Low Word)
4X+2 (High Word)
Maximum Count for Counter 2 (max = 7FFFFFFF hex)
16151413121110987654321
4X+3 (Low Word)
4X+4 (High Word)
Configured for two 32 bit Counters - NO Output Assert